GMV DC Inverter VRF
58
If master unit displays as below, system is waiting for confirmation signal.
12_Status
judgments of
outdoor valves
before startup
Ready for units to start debugging.
If it’s confirmed, press SW7 confirmation button. Unit will display as below and start next
progress.
12_Status
judgments of
outdoor valves
before startup
Manual calculation of refrigerant
quantity is set up.
Step 17:
after unit is confirmed to start debugging, system select cooling/heating mode
according to ambient temperature.
A If cooling mode is selected, relevant display is as below:
Debugging is enabled in cooling mode
(debugging mode, auto-selected by
system).
Error occurs during debugging in
cooling mode.
Error of other modules occurs during
debugging in cooling mode.
Outdoor pipeline and valves are not
normal.
System detects error in indoor
pipeline. XXXX is the project no. of the
faulted IDU. 3s later, error code U8 is
displayed. For example, IDU no. 100
has U8 error, then LED3 displays like
this: 01 (2s later) 00 (2s later) U8, and
repeat again.