GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
319
Possible cause:
The database for the Remote Monitoring System on the server is not enabled.
Solution:
(1) Check whether the database for the Remote Monitoring System in the server is enabled. Right click
―My computer‖ and choose ―Manage‖ from the shortcut menu, and choose ―Services and Applications‖
-> ―Services‖ to check whether the SQL Server (SQLEXPRESS) is running; if not, right click it and
choose ―Start‖. If SQL Server is not found, maybe SQL Server setup fails. Unload the software and
reinstall it; or manually install SQL Server 2008 R2 and then install this software.
(2) During self-check, ―BAS system service has been stopped‖ is prompted, as shown in the following
figure: