GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
192
4. Check oil return pipes.
Remove oil return pipes and balance pipes, and check oil volume and impurity.
Note: Before replacing the faulty parts, make sure to block their openings with tapes. They
should be kept intact for further analysis.
Note: Volumes of oils drawn out from the oil separator, gas separator, and oil balancer should
be recorded. After faulty compressors and parts are replaced, you should fill new oils of
equivalent amount into the compressors and parts.
Step 6: Clear pipeline system.
Check pipelines for abnormalities. Charge nitrogen into the main pipeline and clear the pipeline system.
Clear the balance pipes.
Components of oil balance valve 1:
Remove
oil return
pipes
Remove balance
pipes