GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 
195 
should be blocked. If the sealing rubber is not available, cover them with tape to prevent direct contact of 
oil and air.   
 
Note: The new compressor must be consistent with the faulty one in model.   
Prevention against electric shock
Turn power off before servicing. Use this compressor on a grounded system only. 
Warning
AND-NOT
Prohibition
DO NOT put flammable or explosive gas into the compressor. 
 
Check the rubbers for oil separator, gas separator, oil balancer, and drying filter. If they are lost during 
transportation, cover the parts with tape to keep the compressor dry and airtight inside.   
The rubbers 
used for 
blocking the 
inlet and outlet 
of compressors 
must be intact 
The cover of the 
electric box 
should be intact