(2) Press  SW2  (▼)  on  the controlling unit  and  select  n5. Short press  SW7  to show the following 
information: 
(3) When project number deviation is to be confirmed, short press SW7 confirmation button to enter 
the project number deviation status as shown in the following: 
IDU project numbers in all systems will automatically deviate. The conflict will be solved in about 1 
minute and the system will work properly.   
The automatic deviation function only works when it is enabled on the controlling unit in the system, 
of which the centralized control address is 00000.   
Note:
 When there are only a few conflicting IDUs, manual setting is recommended. This method 
only applies to conflicting IDUs and does only affect other IDUs' project numbers.   
In case of many conflicting IDUs, auto deviation is recommended. This method is faster, but may 
change  project  numbers  of  normal  IDUs.  This  method  applies  for  the  first  commissioning  after 
installation.   
Communication 
failure between main 
control board and 
inverter compressor 
drive 
1.The control board is powered off; 
2.The compressor drive board is powered 
off; 
3.The communication cable between the 
control board and compressor drive board 
is not connected; 
4.The compressor drive board's dial 
switch SA201 is wrong. 
1.Check the power supply of the control 
board. Replace the control board if it works 
properly; 
2.Check the power supply of the drive 
board. Replace the drive board if it works 
properly; 
3.Connect the main board and drive board 
using the communication cable; 
4.Adjust the dial switch of the compressor 
drive board. 
Compressor drive 
module reset 
protection 
1.The compressor drive board is faulty. 
1.Replace the compressor drive board. 
Inverter compressor 
over-current 
protection 
1.The drive board's IPM module is 
damaged; 
2.The compressor's UVW cable is not 
connected properly;   
3.The compressor is damaged. 
1.Replace the compressor drive board;   
2.Reconnect the compressor's UVW cable; 
3.Replace the compressor. 
Compressor drive 
IPM module 
protection 
1.The drive board's IPM module is 
damaged; 
2.The compressor's UVW cable is not 
connected properly;   
3.The compressor is damaged. 
1.Replace the compressor drive board;   
2.Reconnect the compressor's UVW cable; 
3.Replace the compressor. 
Compressor drive 
temperature sensor 
fault 
1.The compressor drive board is faulty. 
1.Replace the compressor drive board. 
Compressor drive 
IPM 
over-temperature 
protection 
1.The compressor drive board is faulty; 
2.Thermal gel is not applied evenly on the 
IPM module; 
3.The IPM module is not screwed 
properly. 
1.Replace the compressor drive board; 
2.Apply thermal gel evenly on the IPM 
module; 
3.Screw the IPM module properly.