GREE                                                                        GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 
    230   
2.2.4.131 “U0” Insufficient compressor preheating time  
Error  display: 
ODU  mainboard,  IDU  wired  controller  and  IDU  receive  light  board  will 
display
 
Error judgment condition and method: 
If it is detected that the oil temperature preheating time of compressor before startup doesn’t reach 8 
hours, it will report this error. 
Possible reason:—— 
Troubleshooting: 
The complete unit shall be preheated for more than 8 hours before startup. 
2.2.4.132 “U2” ODU capacity DIP switch/jumper cap setting error 
Error  display: 
ODU  mainboard,  IDU  wired  controller  and  IDU  receive  light  board  will 
display
 
Error judgment condition and method: 
ODU mainboard detects that the capacity code doesn’t comply with the actual unit capacity, or ODU 
mainboard detects that the jumper cap value doesn’t comply with the actual unit 
Possible reason: 
■Capacity DIP switch is wrong or jumper cap is wrong (for those models without jumper cap, it won’t 
be detected) 
■DIP switch or jumper cap is broken 
■Detecting circuit is abnormal 
Troubleshooting:
 
 
2.2.4.133 “U3” Power phase sequence protection 
Error  display: 
ODU  mainboard,  IDU  wired  controller  and  IDU  receive  light  board  will 
display
 
Error judgment condition and method: 
If phase loss or reverse of three-phase power is detected (e.g. incorrect connection of power supply