GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
271
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
9. Check and then
install the front
panels.
●Check various parts and connecting
lines.
●If no problem is found, hook the
front panels and tighten the screws.
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
1. Loosen the hooks at
the bottom of the
electric box and the
screws.
●
Remove the upper and lower front
panels.
●
Loosen the hooks at the bottom of
the electric box.
●
Use a screwdriver to unscrew the
electric box.
2. Remove the electric
box.
●Disconnect internal and external
connecting lines of the electric box.
●Protect the internal parts during the
disassembly.