GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
278
Gas/liquid separator
Precondition: No refrigerant exists in the pipeline system and the power supply has been disconnected.
Step
Diagram
Operation Procedure
2. Remove the electric
box.
●Disconnect internal and external
connecting lines of the electric
box.
●Protect the internal parts during
the disassembly.
3. Disassemble the
gas/liquid separator.
●Heat the connecting pipes of the
gas/liquid separator by acetylene
welding and then remove the
pipes.
Note: Avoid nearby parts from
being burnt during welding.
4. Remove the
gas/liquid separator.
●Unscrew and remove the
gas/liquid separator.