GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
76
2) On the same refrigerating system, the centralized control address DIP switch (SA2_Addr-CC) on
a non-master unit is invalid, and it is unnecessary to change the settings.
3) The centralized control address DIP switch (SA2_Addr-CC) on the master unit of a refrigerating
system must be set to 0000
×
, and this system is the master system.
4) The centralized control address DIP switch (SA2_Addr-CC) on the master unit of other
refrigerating systems must be set as follows:
SA2
Address No.
DIP1
DIP2
DIP3
DIP4
DIP5
1
0
0
0
×
2
0
1
0
0
×
3
1
1
0
0
×
4
0
0
1
0
×
5
1
0
1
0
×
6
0
1
1
0
×
7
1
1
1
0
×
8
0
0
0
1
×
9
1
0
0
1
×
10
0
1
0
1
×
11
1
1
0
1
×
12
0
0
1
1
×
13
1
0
1
1
×
14
0
1
1
1
×
15
1
1
1
1
×
16
On the DIP switch, ON indicates 0 status and the opposite direction indicates "1 status.
×
indicates invalid status.
5) The centralized control address DIP switch (SA2_Addr-CC) cannot be the same between
different refrigerating systems. Otherwise, address conflicts may occur and the unit cannot run
properly.
6) Suppose the centralized control address (SA2-Addr-CC) of the master unit for one GMV system
is set to 1 1 1 1 X, this system is the master mode system and its running mode will take the
priority. That is, the running mode of the indoor units of other systems cannot conflict with that of
this master mode system. For instance, when the running mode of the master mode system is set
to cooling, it for the indoor units of other systems cannot be set to heating.
Compressor Emergency Operation DIP Switch (SA3_COMP-E)
Corresponding to 2#-6# compressors, the compressor emergency operation DIP switch
(SA3_COMP-E) is used for aftersales emergency settings when an exception occurs on a compressor. It
can shield the operation of the abnormal compressor in a short time and guarantee the emergency
operation of other compressors.
When it is required to shield the operation of 2#-6# compressors upon failure, set the DIP switch
according to the following methods:
Compressor Emergency Operation DIP Switch (SA3_COMP-E)
Remark
DIP1
DIP2
DIP3
DIP4
DIP5
0
0
0
0
0
Not shielding the operation of 2#-6# compressors
1
0
0
0
0
Shielding the operation of 2# compressor