GMV DC Inverter VRF 
54 
board of each module will display: 
If the quantity displayed is the same with actual quantity, then press SW7 confirmation 
button on the master unit to confirm it. Unit will start next progress: 
03_Confirm the 
quantity of 
modules 
If the quantity displayed is different from actual quantity, then disconnect power and check 
whether communication wire among each module is correctly connected. After the check, start 
debugging again. 
Step 8:
 in progress 04, the quantity of IDUs needs to be confirmed manually. Main board 
of each module will display: 
04_Confirm the 
quantity of IDUs 
Quantity of 
connected 
IDUs 
If the quantity displayed is the same with actual quantity, then press SW7 confirmation 
button on the master unit to confirm it. Unit will start next progress: 
04_Confirm the 
quantity of IDUs 
Step 9: 
progress 05 is “Detect internal communication” 
If no error is detected, system will display as below and then start next progress. 
05_Detect 
internal 
communication 
Detection is finished. Start next 
progress.