GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
10
Model
Basic models
Circuit
breaker
capacity
(A)
Circuit breaker
capacity for
combined units
(A
)
Wire size of
power supply
(mm
2
)
Wire size of combined
uni (mm
2
)
GMV-2072WM/B-X
280+ 560+615+615
200
25+63+63+63
2.5+10+10+10
2.5
×
5+10
×
5+10
×
5+10
×
5
GMV-2128WM/B-X
280+615+615+615
200
25+63+63+63
2.5+10+10+10
2.5
×
5+10
×
5+10
×
5+10
×
5
GMV-2184WM/B-X
335+615+615+ 615
200
32+63+63+63
4.0+10+10+10
4.0
×
5+10
×
5+10
×
5+10
×
5
GMV-2240WM/B-X
400+615+615+615
200
40+63+63+63
6.0+10+10+10
6.0
×
5+10
×
5+10
×
5+10
×
5
GMV-2295WM/B-X
450+615+615+615
225
40+63+63+63
6.0+10+10+10
6.0
×
5+10
×
5+10
×
5+10
×
5
GMV-2350WM/B-X
504+615+615+615
225
50+63+63+63
10+10+10+10
10
×
5+10
×
5+10
×
5+10
×
5
GMV-2405WM/B-X
560+615+615+615
225
63+63+63+63
10+10+10+10
10
×
5+10
×
5+10
×
5+10
×
5
GMV-2460WM/B-X
615+615+615+615
225
63+63+63+63
10+10+10+10
10
×
5+10
×
5+10
×
5+10
×
5
For information about the leakage circuit breaker for an indoor unit, refer to the following table. The
circuit breaker capacities listed in the following table indicate the circuit breaker capacities when all
indoor units in the same syatem are connecting connected to the main power.
Total Current Capacity of
Indoor Units
Circuit Breaker
Capacity (A)
Minimum Sectional Area (mm²)
of Power Cable
Minimum Sectional Area (mm²) of
Grounding Wire
Less than 10A
10
1.0
1.0
16~10A
16
1.5
1.5
20~16A
20
2.5
2.5
32~20A
32
4.0
4.0
40~32A
40
6.0
6.0
50~40A
50
10.0
10.0
63~50A
63
16.0
16.0
80~63A
80
25.0
16.0
100~80A
100
35.0
16.0
125~100A
125
50.0
25.0
Table B: The breaker capacity and power cable specifications when a circuit breaker is installed on
each indoor unit independently. Note that the circuit breaker of the indoor unit is used only for
short-circuit protection and abnormal overload of the corresponding indoor unit. Usually, the circuit
breaker is off. All circuit breaker terminals must be connected to one main power switch, which is used to
cut off the power of all indoor units.
IDU
Breaker
Capacity (A)
Minimum Sectional Area of
Power Cable (mm
2
)
Minimum Sectional Area of
Grounding Cable (mm
2
)
Low-static-pressure Air-duct-type Air
Conditioner
6
1.0
1.0
All-dimensional Ceiling Cassette Type
Air Conditioner
6
1.0
1.0
Single-side Air Outlet Ceiling Cassette
Type Air Conditioner
6
1.0
1.0
Floor Ceiling Split Unit
6
1.0
1.0
Wall mounted type Air Conditioner
6
1.0
1.0
Static-pressure Air-duct-type Air
Conditioner
6
1.0
1.0

Table of Contents

Other manuals for Gree GMV-450WM/B-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-450WM/B-X and is the answer not in the manual?

Gree GMV-450WM/B-X Specifications

General IconGeneral
BrandGree
ModelGMV-450WM/B-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals