III. Installation of the Communication System 
The CAN communication network is adopted for GMV5 VRF system. Manual DIP or identification on 
polarities of the communication power is not required for the IDU. Only the function DIP needs to be set 
for the ODU. For details, see the description on function setting of the ODU. 
 
1. Connection of Communication Cable Terminals 
All connections for communication of GMV5 are fastened by screws. 
 
         
 
2. Connection of Communication Cables 
The communication bus of indoor and ODUs must be connected in series instead of in star mode. The 
last IDU of the bus shall be connected to a matching resistor (placed in the package of the ODU).