GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
54
Rated capacity of indoor unit C(kW)
Pipe between indoor branch and IDU
Gas Pipe(mm)
Liquid Pipe(mm)
C2.8
Φ9.52
Φ6.35
2.8C5.0
Φ12.7
Φ6.35
5.0C14.0
Φ15.9
Φ9.52
14.0C16.0
Φ19.05
Φ9.52
16.0C28.0
Φ22.2
Φ9.52