GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
85
2. Introduction to Functions
2.1 List of functions
Function
Code
Function Name
Function Meaning
Factory Settings
Remark
Code
Meaning
A2
Refrigerant
recovery operation
Fully or partially recovers
refrigerants in a faulty module
or IDU pipeline according to
the system pressure after
automatic startup during
maintenance.
——
——
It can only
be set.
A6
Unit
cooling/heating
function
Sets the unit to
cooling/heating,
single-cooling,
single-heating, or air supply
mode for centralized
management.
nA
Cooling/Heating
function
It can be set
and queried.
A7
Outdoor silent
mode
Sets different silent modes to
meet users' noise
requirements.
00
No silent
settings
It can be set
and queried.
A8
Aftersales
vacuuming mode
Automatically
enables all electronic
expansion valves and
electromagnetic valves
during maintenance to
guarantee vacuum
processing in all pipelines.
——
——
It can only
be set.
n0
Conservation
control 1
Automatically decreases the
power consumption of the
unit according to system
operation parameters.
01
No automatic
conservation
settings
It can be set
and queried.
n3
Forcible defrosting
operation
Forcibly enables ODU
defrosting operation.
——
——
It can only
be set.
n4
Conservation
control 2
Forcibly decreases
the maximum power
consumption of the unit.
00
No capacity
output limitation
settings
It can be set
and queried.
n5
Indoor unit project
number offset
Prevents IDU project number
conflicts when different
refrigerating systems are
controlled in a centralized
manner.
——
——
It can only
be set.
n6
Fault query
Queries historical fault
information of the ODU.
——
——
It can only be
queried.
n7
Parameter query
Queries real-time operation
parameters of the ODU.
——
——
It can only be
queried.
n8
Indoor unit project
number query
Displays project numberes of
all IDUs through ODU
operations.
——
——
It can only be
queried.
n9
Online IDU
quantity query
Displays the number of
online IDUs.
——
——
It can only be
queried.
nb
Outdoor unit bar
code function
query
Queries the entire-unit bar
code and controller bar code
of ODU.
——
——
It can only be
queried.
2.2. Description of Functions
(1) A2 Refrigerant recovery operation
This function partially recovers refrigerants in a faulty module or IDU pipeline during unit maintenance.
The refrigerant recovery volume of each basic module is as follows:

Table of Contents

Other manuals for Gree GMV-450WM/B-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-450WM/B-X and is the answer not in the manual?

Gree GMV-450WM/B-X Specifications

General IconGeneral
BrandGree
ModelGMV-450WM/B-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals