GMV5 DC INVERTER VRF UNITS SERVICE MANUAL
89
Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows:
On the master unit, press "SW6" to return to the upper level (press "SW6" in setting status to return to
the upper level; press "SW6" after settings are completed to restore the normal operating status of the
unit).
If no button operations are performed on the master unit for five minutes, the function setting
automatically quits and the unit restores the current status.
The default factory setting is ―00‖, that is, no silent mode.
A6 Unit cooling/heating function settings
Step 1: Confirm entering the A6 unit cooling/heating function settings. The master unit is displayed as
follows:
Step 2: Select a corresponding cooling/heating function by pressing "SW1 (UP)" or "SW2 (DOWN)".
Step 3: Press "SW7" to confirm selecting the mode. The master unit is displayed as follows: