Gree GMV6 DC Inverter VRF Units Service Manual
167
2.130 "P6" IPM Module Protection for the Compressor Drive
Fault display: main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is P6, it
indicates the IPM module protection for the compressor drive.
Possible causes:
■ Poor contact of compressor's UVW cables;
The compressor's UVW cables are wrongly connected;
The compressor is damaged;
The system is blocked;
■ IPM module of the compressor drive board is damaged.
Troubleshooting: