Gree GMV6 DC Inverter VRF Units Service Manual
290
Appendix 2 Refrigerant Temperature and Pressure Table
Refrigerant: R410A
Temperature
(°C)
Corresponding
saturation
pressure (BAR)
Temperature
(°C)
Corresponding
saturation
pressure (BAR)
Temperature
(°C)
Corresponding
saturation
pressure (BAR)
-43
1.54
-9
5.96
25
16.4
-42
1.61
-8
6.16
26
16.9
-41
1.68
-7
6.37
27
17.3
-40
1.76
-6
6.58
28
17.8
-39
1.84
-5
6.80
29
18.5
-38
1.93
-4
7.03
30
18.7
-37
2.02
-3
7.26
31
19.2
-36
2.11
-2
7.50
32
19.7
-35
2.24
-1
7.74
33
20.2
-34
2.33
0
7.99
34
20.7
-33
2.43
1
5.94
35
21.2
-32
2.53
2
8.50
36
21.7
-31
2.64
3
8.77
37
22.3
-30
2.75
4
9.04
38
22.8
-29
2.86
5
9.32
39
23.4
-28
2.98
6
9.61
40
24.0
-27
3.10
7
9.90
41
24.6
-26
3.22
8
10.2
42
25.2
-25
3.35
9
10.5
43
25.8
-24
3.48
10
10.8
44
26.4
-23
3.61
11
11.1
45
27.0
-22
3.75
12
11.5
46
27.7
-21
3.89
13
11.8
47
28.3
-20
4.04
14
12.1
48
29.0
-19
4.19
15
12.5
49
29.6
-18
4.35
16
12.8
50
30.3
-17
4.51
17
13.2
52
31.7
-16
4.67
18
13.6
54
33.2
-15
4.84
19
14.0
56
34.7
-14
5.02
20
14.4
58
36.3
-13
5.19
21
14.7
60
37.9
-12
5.38
22
15.2
62
40.17
-11
5.57
23
15.6
65
42.78
-10
5.76
24
16.0
67
44.57