D.C. Inverter Multi VRF Modular
49
pipe or at least 70% of the needed refrigerant has been added.
(6) Description of each stage of debugging progress:
Description of each stage of debugging progress
——
Debugging
code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
01_Set up
master unit
db
light
01
light
A0
light
System is not debugged.
db
light
01
light
CC
light
System doesn’t have master unit. Reset
master unit.
db
light
01
light
CF
light
More than 2 master units are set. Reset
master unit.
db
light
01
light
OC
light
Master unit is successfully set. Start next
progress.
Description of each stage of debugging progress
——
Debugging
code
Progress code
Status code
Meaning
progress
LED1
LED2
LED3
Code
Display
status
code
Display
status
Code
Display
status
02_Allocate
addresses
db
light
02
light
Ad
blink
System is allocating addresses.
db
light
02
light
L7
blink
Master IDU is not set. Please set master
IDU. If it’s not set in 1min, system will set
the master IDU randomly.
db
light
02
light
OC
light
Allocation is finished. Start next
progress.
03_Confirm the
quantity of
modules
db
light
03
light
01~04
blink
LED3 displays the quantity of modules.
Confirm the number manually.
db
light
03
light
OC
light
System has confirmed the quantity of
modules. Start next progress.
04_Confirm the
quantity of IDUs
db
light
04
light
01~80
blink
LED3 displays the quantity of IDUs.
Confirm the number manually.
db
light
04
light
OC
light
System has confirmed the quantity of
IDUs. Start next progress.
05_Detect
internal
communication
db
light
05
light
C2
light
System detects “driven communication
error between master unit and inverter
compressor”.
db
light
05
light
C3
light
System detects “driven communication
error between master unit and inverter
fan”.
db
light
05
light
CH
light
IDU/ODU “high proportion of rated
capacity”.
db
light
05
light
CL
light
IDU/ODU “low proportion of rated
capacity”.
db
light
05
light
OC
light
Detection is finished. Start next progress.
06_Detect
outdoor
db
light
06
light
Error code
light
System detects error in outdoor
components.

Other manuals for Gree GMV-615WM/B-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-615WM/B-X and is the answer not in the manual?

Gree GMV-615WM/B-X Specifications

General IconGeneral
BrandGree
ModelGMV-615WM/B-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals