76
No.
Debugging project
Parameters name
Unit
Reference value
for the system is -15~8ć.
6
Opening angle of
electrocnic
expansion valve
for heating
PLS
●During cooling operation, the electronica expansion valve
for heating will always be kept at 480PLS;
●During heating operation, the ope
ning angle for the
adjusted electronic expansion valve is 55~480PLS.
7
Operation
frequency for
compressor
HZ
Change among 10HZ~
95HZ
8
Operation current
of compressor
A
Current should be no more than 25.0A during normal
operation for compressor
9
IPM module
temperature for
compressor
ć
When ambient temperature is lower than 35ć, temperature
for IPM module is lower than 80
ć. The maximum
temperature won’t exceed 95
ć
.
10
Operation
frequenc for fan
HZ
It will adjust the frequency among 0~49HZ for operation
according to the system pressure
11
Parameters
of indoor
unit
Ambient
temperature for
indoor unit
ć
——
12
Entry tube
temperature for
indoor heat
exchanger
ć
●According to the difference of ambient temperature, the
entry tube temperature is 1
ć~7ć
lower than the exit tube
temperature for the same indoor unit under cooling mode;
4~9
ć higher than low pressure.
●Under heating mode, entry temperature is 10
ć~20ć
lower than exit tube temperature for the sae indoor unit.
13
Entry tube
temperature for
indoor heat
exchange
ć
14
Opening
angle of
indoor electrocnic
expansion valve
PLS
Under cooling mode, the opening angle for indoor electronic
expansion valve is adjusted among 70~480PLS.
Under heating mode, the opening angle for indoor unit is
adjusted among 40~480PLS.
15
Communication
paraters
Communication
data
Through debugging software, it detected that the quantity of
indoor unit is same with the enginerring actural quantity.
There’s no communication malfunction.
16
Drainage syste ——
Water can be drained smoothly for indoor unit; Outdoor unit
can drain water fromo drainage pipe completely.
17
Other
——

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-80WL/C-T and is the answer not in the manual?

Gree GMV-80WL/C-T Specifications

General IconGeneral
BrandGree
ModelGMV-80WL/C-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals