EasyManua.ls Logo

Gree GMV-950WM/G-X

Gree GMV-950WM/G-X
305 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Gree GMV6 DC Inverter VRF Units Service Manual
78
Possible causes: --
Troubleshooting: not required.
2.10 "AF" Fan State
Fault display: main board of outdoor unit displays
Fault diagnosis:
This is a status code. It indicates that the system has entered the fan mode. In this case, all the
indoor units operate only in fan mode.
Possible causes: --
Troubleshooting: not required.
2.11 "AE" Artificial Refrigerant Charging State
Fault display: main board of outdoor unit displays
Fault diagnosis:
This is a status code. It indicates that the system has employed artificial refrigerant charging mode.
Possible causes: --
Troubleshooting: not required.
2.12 "AJ" Filter Clean Prompt
Fault display: wired controller of indoor unit and receiver of indoor unit display
Applicable models: all indoor units
Fault diagnosis:
This is a status code. It indicates that the filter of indoor unit needs to be cleaned. The cleaning
interval of filter can be set according to actual circumstances.
Possible causes: --
Troubleshooting: Clean the filter and remove the prompt to have the filter proceeds to the next
service cycle.
2.13 "AP" Unit Commissioning Startup Confirmation
Fault display: main board of outdoor unit displays
Fault diagnosis:
This is a status code. It indicates that the unit has been commissioned and is ready for operation.
Possible causes: --
Troubleshooting: not required.
2.14 "AU" Remote Control for Emergency Stop
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display

Other manuals for Gree GMV-950WM/G-X

Related product manuals