GREE GMV5 INDOOR UNIT SERVICE MANUAL
66
5.1.5 Engineering Parameter Query
Engineering parameters can be queried in power-on or power-off status.
Press and hold the FUNCTION button for five seconds to enter the engineering parameter query
interface. The temperature area displays C00 and View is on.
(1) Within five seconds after C00 is displayed, continuously press the MODE button for three
times in an interval less than one second to enter engineering parameter query.
(2) Select a parameter code by pressing or .
(3) Press the ENTER/CANCEL button to return to the upper-level menu till quitting parameter
query.
In the engineering parameter query interface, users can also query user parameters listed in Table
3.1.
The engineering parameter query list is as follows:
Table 2.3 Engineering Parameter Query List
Parameter
Code
Parameter Name
Parameter
Range
View Method
C00
Parameter setting
ingress (default)
-
Display mode:
Timer area: displays the project number of the current IDU.
Note: If the current HBS network consists of multiple IDUs, only
the IDU that has the minimum project number is displayed.
C02
Indoor unit
capacity query
-
Operation method:
In C02 status, press the MODE button to enter the
preferential operation query interface. Press or to
switch the project number of IDU.
Display mode:
Temperature area: displays the project number of the current
IDU.
Timer area: displays the current IDU capacity/IDU capacity after
adjustment.
C04
Project number
query of master
IDU
1-255: project
number
00: no master
IDU
Timer area: displays the project number of the master IDU/00.
C05
Historical fault
query ingress of
IDU
Five historical
faults
Operation method:
1. In C05 status, press the MODE button to enter the
historical fault query interface. Press or to switch the
project number of IDU. Press the MODE button to enter fault
code query of the current IDU. Press or to switch the
fault SN. Press the ENTER/CANCEL button to return to the
upper-level menu.
Display mode:
Temperature area: displays the fault SN and fault code.
Timer area: displays the project number of IDU.
C10
Static pressure
setting query of
ODU
00: 0 Pa
20: 20 Pa
50: 50 Pa
82: 82 Pa
Operation method:
In C10 status, press the MODE button to enter static
pressure setting query of ODU. Press or to switch the
ODU address.
Display mode:
Temperature area: displays the address of the current ODU.
Timer area: displays the static pressure setting value.
C13
Outdoor unit
network number
query
1-255
Timer area: displays the network number of the current ODU.

Table of Contents

Other manuals for Gree GMV-N140U/A-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-N140U/A-T and is the answer not in the manual?

Gree GMV-N140U/A-T Specifications

General IconGeneral
BrandGree
ModelGMV-N140U/A-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals