GREE GMV5 INDOOR UNIT SERVICE MANUAL
67
Parameter
Code
Parameter Name
Parameter
Range
View Method
C14
Temperature
query for inlet-
tube temperature
sensor of IDU
-9 to 99
Operation method:
In C14 status, press the MODE button to enter inlet-tube
temperature sensor query of IDU. Press or to switch
the IDU SN.
Display mode:
Temperature area: displays the project number of the current
IDU.
Timer area: displays the temperature value.
If the HBS network consists of only one IDU, the timer area
directly displays the temperature value in the C14 interface.
No matter Fahrenheit or Centigrade remote signals are
received, the temperature is displayed in Centigrade.
When the wired controller displays the inlet-tube temperature
after receiving signals from the remote controller, the inlet-tube
temperature of the IDU that has the minimum project number in the
HBS network is displayed by default.
C15
Temperature
query for outlet
temperature
sensor of IDU
-9 to 99
Operation method:
In C15 status, press the MODE button to enter outlet
temperature sensor query of IDU. Press or to switch
the IDU SN.
Display mode:
Temperature area: displays the project number of the current
IDU.
Timer area: displays the temperature value.
If the HBS network consists of only one IDU, the timer area
directly displays the temperature value in the C14 interface.
No matter Fahrenheit or Centigrade remote signals are
received, the temperature is displayed in Centigrade.
When the wired controller displays the inlet-tube temperature
after receiving signals from the remote controller, the inlet-tube
temperature of the IDU that has the minimum project number in the
HBS network is displayed by default.
C16
Opening degrees
query of
electronic
expansion valve
of IDU
0-20
Operation method:
In C16 status, press the MODE button to enter electronic
expansion valve opening degree query of IDU. Press or
to switch the IDU SN.
Display mode:
Temperature area: displays the project number of the current
IDU.
Timer area: displays the opening degree value.
If the HBS network consists of only one IDU, the timer area
directly displays the opening degree value of electronic
expansion valve in the C16 interface.
When the wired controller displays the opening degree of
electronic expansion valve after receiving signals from the
remote controller, the opening degree of electronic expansion
valve of the IDU that has the minimum project number in the
HBS network is displayed by default.
n2
Capacity
configuration ratio
upper-limit of
outdoor/IDU
35: 135%
50: 150%
Temperature area: displays the parameter code.
Timer area: displays the setting value of capacity configuration
ratio of the current outdoor/IDU.

Table of Contents

Other manuals for Gree GMV-N140U/A-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-N140U/A-T and is the answer not in the manual?

Gree GMV-N140U/A-T Specifications

General IconGeneral
BrandGree
ModelGMV-N140U/A-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals