Multi Variable Air Conditioners Console Type Indoor Unit 
12 
NOTES!
 
The power of every indoor unit should be unity power supply. 
①
  The power connection cord has been inserted on the mainboard through the piping hole of 
the chassis. Please connect the power connection cord with the breaker. If the power cord is 
not long enough, please prolong it with terminal block.  
 
②
  Reinstall the wiring cover on the original place and tighten the bolt. 
③
  Recover the surface panel. 
CAUTION! 
①
  Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they 
may cause overheating, electrical shock, or fire. 
②
  Do not use locally purchased electrical parts inside the product (Do not branch the power for 
the drain pump, etc, from the terminal block). Doing so may cause electric shock or fire. 
Install the drainage pipe. 
(1)  For well draining, the drain hose should be placed at a downward slant. 
(2)  Do not wrench or bend the drain hose or flood its end by water.   
(3)  Wrap heat resistant material when connect the longer drainage tube though indoor.   
 
Install the connection pipes. 
Connect the connect pipe with the two relative leading pipe, tie the nut on tie in of the connect 
pipe tightly. 
NOTES!
 
①
  Be careful in bending the connection pipes, or you will damage the pipes. 
②
  If the tightening torque is too great in tightening the flare nut, leakage will happen. 
2.5 Wiring Requirements 
Model  Power Cord Size  Air Switch Capacity(A)
Area of Ground 
2
Area of Power 
2
GMV-ND22C/A-T 
GMV-ND28C/A-T 
GMV-ND36C/A-T 
GMV-ND45C/A-T 
220~240V ~ 50Hz 
208~230V ~ 60Hz 
6  1  1