GREE GMV5 INDOOR UNIT SERVICE MANUAL
115
Item
Model
W
H
D
GMV-N56G/A3A-K, GMV-N63G/A3A-K, GMV-N71G/A3A-K, GMV-N56G/A2A-K,
GMV-N63G/A2A-K, GMV-N71G/A2A-K, GMV-N56G/A4A-K, GMV-N63G/A4A-K,
GMV-N71G/A4A-K, GMV-N56G/A8A-K, GMV-N63G/A8A-K, GMV-N71G/A8A-K
GMV-N56G/C9A-K, GMV-N63G/C9A-K, GMV-N71G/C9A-K, GMV-N56G/E3A-K,
GMV-N63G/E3A-K, GMV-N71G/E3A-K, GMV-N56G/B3A-K, GMV-N63G/B3A-K,
GMV-N71G/B3A-K, GMV-N56G/A3A-D, GMV-N63G/A3A-D, GMV-N71G/A3A-D
GMV-N56G/A2A-D, GMV-N63G/A2A-D, GMV-N71G/A2A-D, GMV-N56G/A4A-D,
GMV-N63G/A4A-D, GMV-N71G/A4A-D, GMV-N56G/A8A-D, GMV-N63G/A8A-D,
GMV-N71G/A8A-D, GMV-N56G/C9A-D, GMV-N63G/C9A-D, GMV-N71G/C9A-D
GMV-N56G/E3A-D, GMV-N63G/E3A-D, GMV-N71G/E3A-D, GMV-N56G/B3A-D,
GMV-N63G/B3A-D, GMV-N71G/B3A-D, GMV-ND56G/A3A-T, GMV-ND63G/A3A-T,
GMV-ND71G/A3A-T, GMV-ND56G/A8A-T, GMV-ND63G/A8A-T, GMV-ND71G/A8A-T
1008
221
319
GMV-ND80G/A3A-T, GMV-ND90G/A3A-T, GMV-ND100G/A3A-T
GMV-ND80G/A8A-T, GMV-ND90G/A8A-T, GMV-ND100G/A8A-T
1350
326
258
3.11.2 Installation space
Unit:mm
3.11.3 Installation notice
Connect the ends of the connection pipe with two leading pipes, and then tighten the joint nuts tightly.
Connect the connect pipe with the two relative leading pipe, tie the nut on tie in of the connect pipe
tightly.
Notes:
Be careful in bending the connection pipes, or you would damage the pipes.
If the tightening torque for the flare nut is too great, leakage would happen.
3.11.4 Selection of air switch and power cord
Model
Power Cord Size
Air Switch apacity
(A)
Minimum Sectional Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional Area of
Power Cord
(mm
2
/AWG)
GMV-N22G/A3A-K,
GMV-N22G/A2A-K
GMV-N22G/A4A-K,
GMV-N22G/A8A-K
GMV-N22G/C9A-K,
GMV-N22G/E3A-K
GMV-N22G/B3A-K,
220-240V ~
50Hz
6
1.0/AWG18
1.0/AWG18

Table of Contents