GREE                                                                                          GMV5 INDOOR UNIT SERVICE MANUAL   
 
67 
 
Temperature 
query for inlet-
tube temperature 
sensor of IDU 
Operation method: 
In “C14” status, press the “MODE” button to enter inlet-tube 
temperature sensor query of IDU. Press “ ” or “ ” to switch 
the IDU SN. 
Display mode: 
Temperature area: displays the project number of the current 
IDU. 
Timer area: displays the temperature value. 
If the HBS network consists of only one IDU, the timer area 
directly displays the temperature value in the “C14” interface. 
No matter Fahrenheit or Centigrade remote signals are 
received, the temperature is displayed in Centigrade. 
When the wired controller displays the inlet-tube temperature 
after receiving signals from the remote controller, the inlet-tube 
temperature of the IDU that has the minimum project number in the 
HBS network is displayed by default. 
Temperature 
query for outlet 
temperature 
sensor of IDU 
Operation method: 
In “C15” status, press the “MODE” button to enter outlet 
temperature sensor query of IDU. Press “ ” or “ ” to switch 
the IDU SN. 
Display mode: 
Temperature area: displays the project number of the current 
IDU. 
Timer area: displays the temperature value. 
If the HBS network consists of only one IDU, the timer area 
directly displays the temperature value in the “C14” interface. 
No matter Fahrenheit or Centigrade remote signals are 
received, the temperature is displayed in Centigrade. 
When the wired controller displays the inlet-tube temperature 
after receiving signals from the remote controller, the inlet-tube 
temperature of the IDU that has the minimum project number in the 
HBS network is displayed by default. 
Opening degrees 
query of 
electronic 
expansion valve 
of IDU 
Operation method: 
In “C16” status, press the “MODE” button to enter electronic 
expansion valve opening degree query of IDU. Press “ ” or 
“ ” to switch the IDU SN. 
Display mode: 
Temperature area: displays the project number of the current 
IDU. 
Timer area: displays the opening degree value. 
If the HBS network consists of only one IDU, the timer area 
directly displays the opening degree value of electronic 
expansion valve in the “C16” interface. 
When the wired controller displays the opening degree of 
electronic expansion valve after receiving signals from the 
remote controller, the opening degree of electronic expansion 
valve of the IDU that has the minimum project number in the 
HBS network is displayed by default. 
Capacity 
configuration ratio 
upper-limit of 
outdoor/IDU 
Temperature area: displays the parameter code. 
Timer area: displays the setting value of capacity configuration 
ratio of the current outdoor/IDU.