CONTROL 0 42 0
GMV5 COMPACT MULTI VRF UNIT
SERVICE MANUAL
EC
Loose protection for
discharge temperature
sensor for compressor 1
FJ
Abnormal current
sensor for compressor6
b6
Malfunction of suction
temperature sensor1
EL
Loose protection for
discharge temperature
sensor for compressor 2
FU
Malfunction of casing
top temperature sensor
for compressor1
b7
Malfunction of suction
temperature sensor2
EE
Loose protection for
discharge temperature
sensor for compressor 3
Fb
Malfunction of casing
top temperature sensor
for compressor2
b8
Malfunction for outdoor
ambient humidity sensor
EF
Loose protection for
discharge temperature
sensor for compressor 4
J1
Overcurrent
protection for
compressor 1
b9
Malfunction of gas exit
temperature sensor for
heat exchanger
EJ
Loose protection for
discharge temperature
sensor for compressor 5
J2
Overcurrent protection
for compressor 2
bA
Malfunction of oil return
temperature sensor
EP
Loose protection for
discharge temperature
sensor for compressor 6
J3
Overcurrent protection
for compressor 3
bH
Abnormal clock of
system
F0
Poor main board of
outdoor unit
J4
Overcurrent protection
for compressor 4
bC
Loose protection for
casing top temperature
sensor for compressor 1
F1
Malfunction of high
pressure sensor
J5
Overcurrent protection
for compressor6
bL
Loose protection for
casing top temperature
sensor for compressor 2
F3
Malfunction of low
pressure sensor
J6
Overcurrent protection
for compressor 6
P0
Malfunction driven
board for compressor
F5
Malfunction of discharge
temperature sensor of
compressor 1
J7
Air-mixing
protection for 4-way
valve
P1
Driven board of
compressor works
abnormally
F6
Malfunction of discharge
temperature sensor of
compressor 2
J8
High pressure ratio
protection of system
P2
Power voltage protection
for the driven board of
compressor
F7
Malfunction of discharge
temperature sensor of
compressor 3
J9
Low pressure ratio
protection of system
P3
Reset protection for the
driven module of
compressor
F8
Malfunction of discharge
temperature sensor of
compressor 4
JA
Abnormal pressure
protection
H0
Malfunction driven
board for fan
F9
Malfunction of discharge
temperature sensor of
compressor 5
JC
Waterflow switch
protection
H1
Driven board of fan
works abnormally
FA
Malfunction of discharge
temperature sensor of
compressor 6
JL
High pressure is too
low
H2
Power supply voltage
protection of fan motor
drive board

Other manuals for Gree GMV5 Compact Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 Compact Series and is the answer not in the manual?

Gree GMV5 Compact Series Specifications

General IconGeneral
BrandGree
ModelGMV5 Compact Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals