The system pipe is blocked 
Use pressure gauge to measure if 
the pressure is really high? 
Check if the operation mode of 
indoor unit is set properly? 
Check if the gas valve and liquid 
valve are fully open? 
Check if the front panel of outdoor 
unit is covered tightly? 
Check if the air inlet and outlet of 
the indoor and outdoor exchanger 
is smooth? 
Check if the indoor and outdoor 
fans run normally? 
Check if the indoor swing louver is 
fully open? 
Check if the capacity output of 
outdoor unit is equal to the 
capacity demand of indoor units? 
Check if the indoor electronic 
expansion valve can work 
normally 
Check if the indoor / outdoor filters 
or radiating fins are dirty or 
blocked? 
High-pressure protection 
Measure if the pressure switch is 
normal? 
Replace the mainboard of outdoor unit 
Replace the pressure switch Refer to the Instruction Manual for Indoor Unit 
Fully open the valve 
Cover up the front panel properly 
Remove the obstructions 
Measure the fan motor and signal input 
Measure the swing motor and signal input 
Refer to the dial-up of indoor and outdoor unit 
Engage the valve body with the coil 
Refer to the Repair and Maintenance 
Focus on checking the inlet and outlet of the connection between indoor units and main pipe. 
Also focus on checking the electronic expansion valve of indoor unit and outdoor unit. Replace 
the electronic expansion valve, drying filter and other parts 
NO 
NO
NO
NO
NO
NO
NO
NO
NO
Yes
NO
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
NO