Air-to-water Heat Pump
18
MONOBLOC
TYPE
Description:
Unit: inch
No. Name Remarks
1 Handle Used to cover or uncover the front case
2 Air discharge Grill /
6.2.3 Space requirements for installation
>1000
>2000
>
500
>
500
>
500
>
500
>
0002
Outlet
Outlet
Inlet
Inlet
Note: In conderation of space restriction, for the left-handed gure, except the outlet side, distance between the
unit and the nearest barrier at other three sides are allowed to be no less than 300mm; for the right-handed gure,
distance between the inlet side and the nearest barrier is allowed to be no less than 300mm.
6.2.4 Precautions on installation of monobloc unit
(1) When moving outdoor unit, it is necessary to adopt 2 pieces of long enough rope to hand the unit from
4 directions. Included angle between the rope when hanging and moving must be 40° below to prevent
center of the unit from moving.
(2) Adopt M12 bolts components to tighten feet and under frame when installing.
(3) Monobloc unit should be installed on concrete base that is 10cm height.
(4) Requirements on installation space dimension of unit’s bodies are shown in following drawing.
(5) Monobloc unit must be lifted by using designated lifting hole. Take care to protect the unit during lift. To
avoid rusting, do not knock the metal parts.
6.2.5 Usage of rubber rings
Water return Water supply
(1) Take away the original rubber rings, replace the long tail rubber rings of accessory;
(2) Wires installed by eld supply get through the rubber rings,such as 2-way valve,3-way valve,power cable
and so on.Be careful of separating electrical wire and light current wire.
(3) Tie the rubber rings after nishing wire connection.