16.4 Requirements on water quality
Paramete Parametric value Unit
pH( 25°C) 6.8~8.0 /
Cloudy
<
1 NTU
Chloride
<
50 mg/L
Fluoride
<
1 mg/L
Iron
<
0.3 mg/L
Sulphate
<
50 mg/L
SiO
2
<
30 mg/L
Hardness(count CaCO
3
)
<
70 mg/L
Nitrate(count N)
<
10 mg/L
Conductance(25°C)
<
300 μs/cm
Ammonia (count N)
<
0.5 mg/L
Alkalinity(count CaCO
3
)
<
50 mg/L
Suld Cannot be detected mg/L
Oxygen consumption
<
3 mg/L
Natrium
<
150 mg/L
Note: when circulation water fails to meet requirements listed in the table above, please add anti-scale
composition to keep the unit always in normal operation.
16.5 Electric wiring work
16.5.1 Wiring principle
General principles
(1) Wires, equipment and connectors supplied for use on the site must be in compliance with provisions of
regulations and engineering requirements.
(2) Only electricians holding qualication are allowed to perform wire connection on the site.
(3) Before connection work is started, the power supply must be shut o.
(4) Installer shall be responsible for any damage due to incorrect connection of the external circuit.
(5) Caution --- MUST use copper wires.
(6) Connection of power cable to the electric cabinet of the unit
(7) Power cables should be laid out through cabling trough, conduit tube or cable channel.
(8) Power cables to be connected into the electric cabinet must be protected with rubber or plastic to prevent
scratch by edge of metal plate.
(9) Power cables close to the electric cabinet of the unit must be xed reliably to make the power terminal in
the cabinet free from an external force.
(10) Power cable must be grounded reliably.