AIR-TO-WATER HEAT PUMP CONTROL
23
20
Setting turn on temperature of back-up
heater(indoor unit)
/
-2018(default:
0)
21
Setting maximum water tank
temperature heated by heat pump cycle
/
40-50(default:
50)
22
Setting heating temperature of
disinfection operation
/
40-70(default:
70)
23
Setting lower temperature for
Weather-dependent operation
/
-205(default:
-15)
24
Setting upper temperature for
Weather-dependent operation
/
1020(default:
15)
25
Setting temperature gap from target
temperature of cooling operation
/
210(default:
5)
26
Setting temperature gap from target
temperature of heating operation
/
210(default:
5)
27
Setting temperature gap from target
temperature of sanitary heating
operation
/
28(default:
3)
3.2.3.4 Function Set-up Description
z Function code 1Setting temperature selection
The unit can operate according to air temperature or outflow water temperature.
The air temperature or outflow water temperature can be selected as setting
temperature.
Note: Air temperature as setting temperature is ONLY available when Remote Air
Sensor Connection is enabled and Function Code 18 is set as 01.
z Function code 2Forced operation
Forced Operation includes forced cooling and forced heating operation:
Forced cooling operation should be performed when additional refrigerant charge is
required.
To charge the refrigerant, the unit must run in Cool mode.
Forced cooling should be performed upon the first runtest runand when out-door
temperature is lower than 10
Forced heating should be performed upon the first runtest runand when out-door
temperature is higher than 35
Forced Operation instantly makes the unit working in Cool/Heat mode for 15
minutes.