Air-to-water Heat Pump
Thank you for choosing commercial air conditioners. Please read
t
his Owner s Manual carefully before operation and retain it for
f
uture reference.
If
you have lost the Owner's Manual,please contact the local agent
or
visit www.gree.com or send an email to global@gree.com.cn for
t
he electronic version.
GREE PRODUCTS, S.L.
Owner's Manual
Original Instructions
Air Conditioners
MONOBLOC
TYPE

Table of Contents

Other manuals for Gree GRS-CQ6.0Pd/NhG-K

Questions and Answers

  • C
    Clarence HunterAug 5, 2025
    What to do if Gree Heat Pump does not heat although compressor is running?
    • R
      rebeccaaguilarAug 5, 2025
      If your Gree Heat Pump isn't heating despite the compressor running, a possible cause is refrigerant leakage, which requires leakage detection and refrigerant replenishment. Another potential cause is a malfunctioning compressor, which would need replacement.
  • W
    William TerryAug 9, 2025
    How to improve hot water heating efficiency of Gree Heat Pump?
    • M
      Mary RobinsonAug 9, 2025
      If your Gree Heat Pump has poor hot water heating efficiency, check for poor heat insulation in the water system and enhance it. Also, check for poor heat exchange of the evaporator by ensuring normal air flow and cleaning the evaporator. Poor refrigerant levels due to leaks can also cause this, so check for refrigerant leaks. Finally, a blockage in the heat exchanger on the water side can reduce efficiency; clean or replace the heat exchanger if needed.
  • J
    Jerry RodriguezAug 13, 2025
    What causes heavy noise of Gree GRS-CQ6.0Pd/NhG-K compressor?
    • R
      rfoxAug 14, 2025
      Heavy noise from the Gree Heat Pump compressor can occur if liquid refrigerant enters the compressor, leading to liquid slugging. Check the expansion valve and temperature sensor for failures or looseness, and repair if necessary. Alternatively, internal parts in the compressor may be broken, requiring compressor replacement.
  • Z
    zbrewerAug 18, 2025
    What to do if Gree GRS-CQ6.0Pd/NhG-K fan makes a heavy noise?
    • G
      Gary DavisAug 18, 2025
      If the Gree Heat Pump fan is making excessive noise, it could be due to a loose fixing bolt, which needs to be re-fixed. Alternatively, the fan blade might be touching the shell or grill, requiring adjustments. Unreliable fan operation may also cause noise, indicating the fan needs replacement.
  • W
    Whitney CopelandAug 22, 2025
    What to do if Gree GRS-CQ6.0Pd/NhG-K water pump does not run?
    • V
      vjordanAug 22, 2025
      If the Gree Heat Pump water pump isn't running or is running abnormally, it could be due to a malfunction in the power supply or terminal, requiring you to find out the reasons and repair it. A malfunctioning relay could also be the cause, necessitating a relay replacement. Another potential issue is air in the water pipe, which needs to be evacuated.
  • Y
    Yvette BeckerAug 26, 2025
    Why won't my Gree GRS-CQ6.0Pd/NhG-K compressor start?
    • R
      Ryan HuntAug 26, 2025
      If the Gree Heat Pump compressor isn't starting, it could be due to a power supply issue such as a reversed phase sequence. It may also be due to loose connection wires, which should be checked and re-fixed. A malfunction of the mainboard or the compressor itself could also be the cause, requiring repair or replacement, respectively.
  • B
    bruizAug 30, 2025
    Why does my Gree Heat Pump compressor start and stop frequently?
    • A
      Ashley BellAug 30, 2025
      If your Gree Heat Pump compressor frequently starts and stops, it could be due to poor or excess refrigerant; in this case you should discharge or add part of the refrigerant. It might also be caused by poor circulation in the water system, potentially due to blockages or air, so inspect the water pump, valve, and pipeline, cleaning the water filter or evacuating air as needed. A low load can also cause this issue; try adjusting the load or adding accumulating devices.

Summary

Safety Notices

Operating Principle of the Unit

Installation Examples

Case 1: Under-floor Coil Installation

Example of connecting under-floor coil for heating and cooling.

Main Components

Installation Guideline of Monobloc Unit

Installation Instructions

General instructions for unit installation.

Monobloc Unit Installation

Specifics on installing the monobloc unit.

Installation Precautions

Safety precautions during unit installation.

Safety Operation of Flammable Refrigerant

Installation of Hydraulic Unit

2-Way Valve

3-Way Valve

Optional Electric Heater

Refrigerant Charging and Discharging

Leak Detection Methods

Methods for detecting refrigerant leaks.

Insulated Water Tank Installation

Installation Measures

Measures and considerations for installing the insulated water tank.

Waterway System Connection

Instructions for connecting the waterway system.

Electric Wiring Work

Guidelines and principles for electric wiring.

Power Supply and Leakage Switch Specifications

Wiring Diagrams

Control Board Wiring

Diagram and explanation of the control board connections.

Electric Wiring Details

Terminal Board Layout

Commissioning

Pre-Startup Checks

Pre-startup checks to ensure safe operation and proper installation.

Test Run Procedure

Daily Operation and Maintenance

Refrigerant Recovery