DRY Mode
The conditions and processes of dehumidifying:
If T
amb
>T
set
+2℃, the cooling mode will act, indoor fan speed could be adjusted, outdoor fan will run.
indoor fan will delay 30secs and stop, after 3.5mins, compressor and outdoor fan will run, and indoor fan will run at the low low speed. The processes of dehumidifying
a re shown as the above cycle.
If Tset -2℃≤Troom≤Tset+2℃,DRY mode will act, the indoor fan will run at the low speed.after running for 6mins, outdoor fan and compressor will stop, but
If T
amb
< T
set
-2℃, the unit will stop, the compressor will stop, after 15sec latter, outdoor fan will stop, after another 15sec, indoor fan will stop.
In this mode, the reversal valve will not power on, the setting temp. range:16℃~30℃.
Protection Functions
Antifreezing Protection
When running in COOL mode, antifreezing protection is the same as the cooling. The DRY mode act, when the antifreezing protection is detected,
the compressor will stop, but outdoor fan will delay 15secs and stop, indoor fan will run at low speed; when antifreezing protection is eliminated and
compressor has stopped for 3min, the whole unit will run at the original status.
HEAT Mode
The conditions and processes of heating
In this mode, the reversal valve will not power on, the setting temp. range:16℃~30℃.
If Tamb ≤Tset+2℃, HEAT mode will act, compressor, outdoor fan and reversing valve will run, but indoor fan will after 20sec delayed and run.
If Tamb≥Tset+4℃, Compressor will stop first, outdoor fan will delay 15s and stop, reversing valve will keep working, after 30secs indoor fan will blow
the surplus heat, after 30secs it will stop.
If Tset+2℃<T set<T set +4℃,the unit will keep running in the old mode.
20
During the antifreezing protection
Fan speed could
be adjusted
During the antifreezing protection
Keep running in the old mode