GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
137
2 Temperature/Pressure List of Refrigerant
R410A
Temperature Pressure
Temperature Pressure
Temperature Pressure
℃ kPa ℃ kPa ℃ kPa
-30 275 0 803 30 1880
-29 286 1 823 31 1910
-28 298 2 851 32 1960
-27 311 3 879 33 2030
-26 324 4 903 34 2080
-25 334 5 937 35 2130
-24 348 6 962 36 2180
-23 363 7 994 37 2240
-22 375 8 1020 38 2290
-21 391 9 1050 39 2350
-20 404 10 1090 40 2410
-19 424 11 1110 41 2460
-18 435 12 1150 42 2510
-17 453 13 1180 43 2580
-16 468 14 1220 44 2650
-15 483 15 1250 45 2710
-14 504 16 1280 46 2770
-13 520 17 1320 47 2840
-12 538 18 1350 48 2910
-11 556 19 1400 49 2980
-10 579 20 1440 50 3050
-9 598 21 1470 51 3100
-8 618 22 1520 52 3180
-7 639 23 1560 53 3250
-6 660 24 1600 54 3320
-5 682 25 1640 55 3400
-4 705 26 1680 56 3480
-3 728 27 1730 57 3540
-2 752 28 1780 58 3630
-1 777 29 1820 59 3720
3 Operation Tools
The following tools will be used: 1) Liquid-level gauge; 2) Screwdriver; 3) Electric driven rotary hammer; 4)
Drill; 5) Pipe expander; 6) Torque wrench; 7) Open-end wrench; 8) Pipe cutter; 9) Leak detector; 10) Vacuum
pump; 11) Pressure gauge; 12) Universal meter; 13) Hexagon wrench; 14) Tapeline