GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
13
Capacity GUD48AH2/D-D(U) Indoor Unit Dip Switches GUD60AH2/D-D(U) Indoor Unit Dip Switches
Level 1
Level 2
Level 3
Level 4
Level 5
Level 6
(Default)
Level 7
Level 8
NOTE:
After the unit is shut down or stopped at the temperature point, the indoor unit will delay for a few minutes
and then shut down. The refrigeration can realize the drying function, relieve the mold of the air duct, and the
heating can blow the waste heat and relieve the heat accumulation in the air duct.
Installation and debugging when attention to verify the switch sequence of electrical heating and fan, ensure
the fan must be turned on when electric heating operation, to ensure the electric heating is turned off before
the fan.
During installation and debugging, pay attention to check whether the temperature controller has set the fan
delay and shutdown time. If the temperature controller has been set, the actual delay and shutdown time of
the fan is equal to the temperature controller setting time plus the fan delay time of the indoor unit.