GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
36
■Poor contact between pressure sensor and terminal in mainboard interface.
■Pressure sensor is abnormal.
■Detecting circuit is abnormal.
Troubleshooting
3.4.9 “EE” Memory chip reading and writing failure
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
If ODU mainboard cannot read the memory chip, this error will be reported.
Possible reason:
Memory chip on the ODU mainboard is damaged.
Memory chip is weakly welded.
Memory chip lead is short-circuited.