GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
49
■Compressor is damaged.
Troubleshooting
:
3.4.23 “Pc” Driver Current Error
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
After power charging, if offset voltage average is detected to exceed 12.5% of 1.65V in 1s, then it can be
judged that current detection (or current sensor) circuit is faulted. System will shut down for protection.
Possible reason:
■Current detection (or current sensor) sampling circuit element is abnormal.
■Drive chip compressor current sampling AD terminal is badly welded or short-circuited.