GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
53
Possible reason:
Voltage of power grid is abnormal. Voltage is too low.
Drive board charge loop element is abnormal.
■Drive board busbar voltage sampling circuit element is damaged or drive chip busbar voltage sampling AD
terminal is abnormal.
Troubleshooting
PU
Charge loop error
Normal protection
Replace the drive board
Grid voltage is too low ?
YES
NO
3.4.28 “A1” Outdoor fan IPM module protection
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
When power is connected and drive chip received IPM lead F0 that is of low level, than it is IPM module
malfunction. System will shut down for protection.
Possible reason:
Outdoor fan 3-phase wire connection is lack of phase or phase-reversed.
System is overloaded and outdoor fan current is too large.
Drive board IPM module is damaged.
Drive board IPM module’s 15V power supply is lower than 13.5V.
Drive board 6-line PWM signal and the corresponding element are abnormal.
Drive board outdoor fan current sampling circuit element is damaged or drive chip current sampling AD
terminal is abnormal.
Compressor is damaged.