GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
70
D- Connect to the exhaust side
Caution! High temperature!
Labels on the 4-way valve:
D-connect to the exhaust side; E-connect to the evaporator of indoor unit.
S-connect to the inhalation side of the liquid separator; C-connect to the condenser.
When the system is in cooling mode, C-the pipeline is with high pressure and high temperature; E, S-the
pipeline is with low pressure and low temperature.
When the system is in heating mode, E-the pipeline is with high pressure and high temperature; C, S-the
pipeline is with low pressure and low temperature.
Because D is connected to the exhaust side, it is with high pressure and high temperature regardless of the
operating mode. When the unit is powered on, in defrosting or oil return mode, the 4-way valve will produce some
noise. Do not touch the pipes directly with your hands and be cautious of the hot temperature.
This is the position of the 4-way
valve. Do not touch it directly
with your hands. There is hot
refrigerant at the exhaust pipe,