DC Inverter U-match Series Floor Ceiling Type Unit 
26 
sealing with insulated cotton in the knock-off hole of outdoor unit to prevent small 
animals from entering. See the following figure. 
   
Notice: 
Only for the GUD100W/NhA-T, GUD125W/NhA-T, 
GUD140W/NhA-T, GUD100W/NhA-X, GUD125W/NhA-X, GUD140W/NhA-X, 
GUD160W/NhA-X units. 
3.2.4 Connection Pipe Vacuum Pumping and Leak Detection 
3.2.4.1 Vacuum Pumping 
Make  sure  the  outlet  of  vacuum  pump  is  away  from  fire  source  and  is 
well-ventilated. 
(1)  Remove the caps of the liquid valve, gas valve and also the service port. 
(2)  Connect the hose at the low pressure side of the manifold valve assembly to the 
service port  of  the  unit’s  gas  valve,  and  meanwhile  the  gas  and liquid valves 
should be kept closed in case of refrigerant leak. 
(3)  Connect the hose used for evacuation to the vacuum pump. 
(4)  Open the switch at the lower pressure side of the manifold valve assembly and 
start the vacuum pump. Meanwhile, the switch at the high pressure side of the 
manifold valve assembly should be kept closed, otherwise evacuation would 
fail. 
(5)  The evacuation duration depends on the unit’s capacity generally. 
GUD71W/NhA-T, GUD85W/NhA-T, 
GUD100W/NhA-T, GUD100W/NhA-X 
GUD125W/NhA-T, GUD140W/NhA-T, 
GUD125W/NhA-X,GUD140W/NhA-X, 
GUD160W/NhA-X