Service Manual
58
Installation and Maintenance
5. Diagnosis for Compressor Synchronism (Outdoor unit malfunction)
Outdoor unit malfunction indicator status
Main detection point:
●If the system pressure is over-high?
●If the working voltage is over-low?
Malfunction diagnosis process:
D5 D6 D16 D30
□ ☆ ■ ☆
If the compressor
wire COMP(UVW) is well connected, the
connection sequence forwards to
clockwise direction?
Check if the fan
terminal OFAN is
connected well
Replace
compressor
If the outdoor fan works
normally?
If the stop time of
compressor is more than
3min
End
Synchronism after
energize the unit
and start it
Connect
wire well