Technical Information
Service Manual
If swing function is set when turning on the unit, the horizontal
louver will swing between L and D.
Horizontal louver has 7 swing statuses:
Stay at position L: control by remote controller:
Stay at position A: control by remote controller:
Stay at position B: control by remote controller:
Stay at position C: control by remote controller:
Stay at position D: control by remote controller:
Swing between L and D: control by remote controller:
Stop at any position between L and D (angles between L and D
are equiangular), control by remote controller: OFF
When turning off the unit, horizontal louver will close at position
O.
Swing action is valid only when swing command has been set
and the IDU fan motor is operating.
b. Left&right swing control
After energization, swing motor will rstly have the vertical
louver rotate anticlockwise to position O to close air outlet. If swing
function has not been set after start-up of the unit, vertical louver
will turn clockwise to position D in heating mode, or turn clockwise
to position L in other modes.
If swing function is set when turning on the unit, the vertical
louver will swing between L and D.
Vertical louver has 7 swing statuses:
Stay at position L: control by remote controller
ǃǃǃǃ
Stay at position A: control by remote controller
ǃǃǃǃ
Stay at position B: control by remote controller
ǃǃǃǃ
Stay at position C: control by remote controller
ǃǃǃǃ
Stay at position D: control by remote controller
ǃǃǃǃ
Swing between L and D: control by remote controller
Stop at any position between L and D (angles between L and D
are equiangular), control by remote controller: OFF
When turning off the unit, vertical louver will close at position O.
Swing action is valid only when swing command has been set
and the IDU fan motor is operating.
L
A
B
C
D
Set this position as starting point 0
0
O
L
A
B
C
D
Set this position as starting point 0
0
O
fan motor operates at low speed.
When Tamb.
Tset-2
, the compressor and the ODU fan
motor stop, while the IDU fan motor runs at low speed.
In drying mode, the 4-way valve is de-energized (4-way valve is
not available for cooling only unit); Temperature setting range is
16
30
. Fan speed can’t be adjusted.
Protection functions (See function protection of this section)
(4)Heating mode(heating mode is not available for cooling
only uni)
Operation condition and process
When Tamb.≤Tset-1
, the system starts heating operation. In
this case, the 4-way valve is energized. The compressor and the
ODU fan motor operates simultaneously; The IDU fan motor will be
started up after delayed for a period of time to make sure the air
conditioner won’t blow out cold wind.
When Tpreset-1
℃<
Tamb.
Tpreset+1
, the system keeps
previous operation status.
When Tamb.≥Tpreset+1
, the compressor and the ODU fan
motor stop. The 4-way valve is energized all the time. The IDU
fan motor will blow residual heat after operating at set speed for a
period of time consecutively to make sure the inner temperature of
air conditioner won’t be too high.
In heating mode, 4-way valve is energized. Temperature setting
range is 16
30
.
Defrosting condition and process
In order to ensure heating effect, the unit will proceed defrosting
automatically according to the frost situation of outdoor unit. Dual-
8 nixie tube displays H1 during defrosting. (For some models,
heating icon is bright for a period of time and then OFF).
Protection functions (See function protection of this section)
(5) Fan mode
Operation condition and process
The IDU fan motor operates at set speed, while the compressor,
the ODU fan motor and 4-way valve stop.
Protection functions (See function protection of this section)
3 Other control function introductions
(1) Swing function (the unit is with up&down swing and
left&right swing)
a. Up&down swing control
After energization, swing motor will rstly have the horizontal
louver rotate anticlockwise to position O to close air outlet. If swing
function has not been set after start-up of the unit, horizontal louver
will turn clockwise to position D in heating mode, or turn clockwise
to position L in other modes.
Defrosting condition and process
In order to ensure heating effect, the unit will proceed defrosting