126
Installation and Maintenance
Service Manual
(6) Overload and air exhaust malfunction diagnosis (following AP1 for outdoor unit control board)
Mainly detect:
●Is the PMV connected well or not? Is PMV damaged?
●Is refrigerant leaked?
Fault diagnosis process:
20 minutes after the 
complete unit is 
powered off
Is the terminal FA for the 
electronic expansion valve 
connected correctly?
Connect the 
wires correctly
Resistances  between  the  first  four  pins 
close to the terminal  hole  and  the  fifth 
pin  are  almost  the  same,  less  than  100 
ohm.
Replace the electronic 
expansion valve
If the fault is eliminated?
If the fault is eliminated?
Replace the 
control panel 
AP1
Coolant leakage, refilling 
the coolant
End
N
N
N
Y