7.IPM protection(H5), desynchronizing malfunction(H7), overcurrent of  compressor  phase current (P5) (AP1 below means 
control board of outdoor unit)
Main detection points:
● 
Is voltage input within the normal range
● 
If the control board AP1 is well connected with compressor COMP? If they are loosened? If the connection sequence is correct?
● 
Heat exchange of unit is not good (heat exchanger is dirty and unit radiating environment is bad);
● 
If the system pressure is too high?
● 
If the refrigerant charging amount is appropriate?
● 
If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
● 
If the work load of unit is heavy? If radiating of unit is good?
Malfunction diagnosis process:
 
N
N
Y
N
Y
Y
Y
N
N
N
N
N
Y
Y
Y
Y
Y
H5, H7 or P5 is 
displayed after 
turning on the unit
Measure if the voltage 
input is within 180~265V 
with AC voltmeter
     (see fig 30)
The compressor 
is well connected
with mainboard 
 AP1?
Heat exchanger is 
blocked with dirt?
Clean the heat exchanger 
to improve its performance
Restart the unit
Restart the unit
Restart the unit
Restart the unit
The unit starts 
operation again
The unit starts 
operation again
The unit starts 
operation again
The unit starts 
operation again
Repair power supply to make 
the power voltage normal
Check if system pressure 
           is too high?
Adjust refrigerant 
charging amount
Replace outdoor 
mainboard AP1
Replace compressor
Does the unit 
work normally
End
Adjust it properly 
according to wiring 
diagram 5.1