27
Service Manual
Technical Information
When 9ć ˘Tindoor amb.˘11ć, indoor unit will operate at medium speed;
When Tindoor amb.≥1
1ćˈindoor fan will operate at low speed;
w high, medium, and low speeds, the minimum operation time is 210 seconds.
2.6.5 If the unit has memory function,
8ćheating function will be memorized.
2.7 Energy-saving Function
2.7.1 In cooling mode,
when receiving command of energy-saving sent by remote control, the controller enters energy-saving mode; If
the unit is under energy-saving mode already,
such command will not be executed.
2.7.2 When remote control is set to display set temperature, “dual 8”nixie tube displays “SE”.
when compressor operates, fan speed will be adjusted according to auto fan mode under energy-saving operation;
en compressor stops operation, indoor fan will operate at low speed.
ć, indoor fan will operate at super high speed;
ć˚Tamb.≥Tpreset + 3ć, indoor fan will operate at high speed;
ć˘Tamb.˘Tpreset + 3ćˈindoor fan will operate at medium speed;
1ćˈ indoor fan will operate at low speed;
The switchover among superhigh speed, high speed, medium speed and low speed requires minimum 210seconds of operation.
2.7.4 In this mode, set temperature
will be automatically adjusted according to actual operation conditions.
3 Other Control
3.1 Timer function
General timer and clock timer functions are compatible by equipping remote controller
with different functions.
mer ON can be set at unit OFF. If selected ON time is reached, the unit will start to operate according to previous setting status. Time
setting range is 0.5-24hr in 30-minute increments.
OFF can be set at unit ON. If selected OFF time is reached, the unit will stop operation. Time setting range is 0.5-24hr in
3.1.2 Clock Timer
Timer ON
If
timer ON is set during operation of the unit, the unit will continue to operate. If timer ON is set at unit OFF, upon ON time reaches the
will start to operate according to previous setting status.
If timer OFF is set at unit OFF, the sy
stem will keep standby status. If timer OFF is set at unit ON, upon OFF time reaches the unit will
Tamb.
Fan speed
Low
Med.
High
Tamb.
Tpreset + 3 ć
31℃
11℃
9℃
Tp ć
Fan speed
Super high
High
Med.
Low
reset + 1