29
Service Manual
Technical Information
3.8 Vertical Swing
3.8.1 Small Horizontal Louver
After
energization, vertical swing motor will firstly have the horizontal louver rotate anticlockwise to position O to close air outlet.
If
sw
ing function has not been set after startup of the unit, horizontal louver will turn clockwise to position D1 in HEAT mode. If swing
function
is set when starting up the unit, the horizontal louver will swing between O and D1.There are 7 swing status of horizontal
louver:
Positions O, A1, B1, C1 and D1, swing between O and D1 and stop at any position between L and D (angles between O an
d
D1
are equiangular). Upon turning off the unit, the horizontal louver will close at position O. Swing function is available only when
sw
ing function is set and indoor fan is operating.
Note:
a.
If the position is set between O and D1, A 1and C1 or B1 and D1 by remote controller, the horizontal louver will swing between
O
and D1.
b.
For model 9K/12K, only when big horizontal louver rotates to the second position for heating( 62°of corresponding angle), this louver
wi
ll be activated
c. Under cooling mode, this horizontal
louver will be always in the position O.
3.8.2 Big Horizontal Louver
A
fter energization, up & down swing motor will firstly have the horizontal louver rotate anticlockwise to position O to close air outlet. If
sw
ing function has not been set after startup of the unit, horizontal louver will turn clockwise to position D in HEAT mode, or turn
cloc
kwise to level position L in other modes. If swing function is set when starting up the unit, the horizontal louver will swing between
L
and
D.There are 7 swing status of horizontal louver: Positions L, A, B, C and D, swing between L and D and stop at any position
be
tween L and D (angles between L and D are equiangular). Upon turning off the unit, the horizontal louver will close at position O.
Note:
If the position is set between L and B, A and C or B and D by remote controller, the horizontal louver will swing between L and D.
3.9 Horizontal Sw
ing
Upon energization, the vertical louver
will be reset to the start position firstly and then stop in the middle position. When setting
Tamb.
Tpreset +3ć
Tpreset
Tpreset -2ć
Mute
(0 degree)
Low High Med.
p
Fan seed
O(0)
A1
B1
C1
D1
L
A
B
C
D
horizontal
swing, there are 7 status: Position ķ, Position ĸ, Position Ĺ, Positon ĺ, Position Ļ, swing between and and stop at
ķĻ
any position be
tween and ķĻ. If setting horizontal swing during operation of the unit, the horizontal swing motor will drive the louver
to sw
ing horizontally. When cancelling horizontal swing or it is not set when turning on the unit, the louver will stop in the current
position and it will not move
when turning off the unit. Only when swing is set and indoor fan is operating, the vertical louver can
horizontally swing.