55
Service Manual
Installation and Maintenance
2. Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit) 
Main detection point: 
● Detect if the voltage of L and N terminal of wiring board is between 210AC-240AC by alternating voltage meter; 
● Is reactor (L) well connected? Is connection wire loosened or pull-out? Is reactor (L) damaged
?
Malfunction diagnosis process: 
N
Y
N
Y
N
Y
N
Y
N
Y
Turn on the unit 
and wait 1 minute
Use DC voltmeter 
to measure the 
voltage on the two 
ends of electrolytic 
capacitor 
Voltage higher than 200V?
Fault with the voltage 
testing circuit on 
control panel AP1
Replace the control 
panel AP1
Measure the AC voltage between 
terminal 
L and N on wiring board 
XT(power supply)
Voltage within 
210VAC~250VAC?
Shut down the power
and repair the power
supply to restore the
range
210VAC~250VAC
power on and
restart the unit
If the fault is 
eliminated?
Shut down the power and wait 20 mi
nutes; or 
use DC voltmeter to measure the voltage 
on the two ends of capacitor (test3), until 
the voltage  is lower than 20V
Check the 
connection of reactor 
(L in the Electrical 
Wiring Diagram)
If the wiring of 
reactor L
 is normal?
Connect the reactor 
Laccording to Elec-
trical Wiring Diagr-
am correctly
 
Re-energize and
turn on the unit
If the fault is 
eliminated?
End
Replace the control 
panel AP1