38
Installation and Maintenance
Service Manual
No. Name No. Name
1 Indoor unit 8 Sealing gum
2 Outdoor unit 9 Wrapping tape
3 Connection pipe 10
Support of outdoor 
unit
4 Drainage pipe 11 Fixing screw
5
Wall-mounting 
frame
12
Drainage plug(cooling 
and heating unit)
6
Connecting 
cable(power cord)
13
Owners manual, 
remote controller
7 Wall pipe
1. Safety Precaution
(1) Must follow the electric safety  regulations  when installing 
the unit.
(2) According  to the  local safety  regulations,  use  qualified 
power supply circuit and air switch.
(3) Make sure the power supply matches with the requirement 
of air conditioner. Unstable  power supply or incorrect wiring 
may result in electric shock,re hazard or malfunction. Please 
install  proper  power  supply  cables  before  using  the  air 
conditioner.
(4) Properly connect the live wire, neutral wire and grounding 
wire of power socket.
(5) Be sure to cut off the power supply before proceeding any 
work related to electricity and safety.
(6) Do not put through the power before nishing installation.
(7)  For  appliances  with  type Y attachment,the  instructions 
shall contain the substance of thefollowing.If the supply cord is 
damaged,it must be replaced by the manufacturer,its service 
agent or similarly qualied persons in order to avoid a hazard.
(8) The temperature of refrigerant circuit will be high, please 
keep the interconnection cable away from the copper tube.
(9) The appliance shall be installed in accordance with national 
wiring regulations.
8.2 Installation Parts-Checking 
8.3 Selection of Installation Location
8.4 Requirements for electric connection
8.5 Installation of Indoor Unit
1.Please contact the local agent for installation.
2.Dont use unqualied power cord.
1. Basic Requirement:
Installing the unit in the following places may cause 
malfunction. If it is unavoidable, please consult the local dealer:
(1) The place with strong heat sources, vapors,  ammable  or 
explosive gas, or volatile objects spread in the air.
(2) The place with  high-frequency devices (such as  welding 
machine, medical equipment).
(3) The place near coast area.
(4) The place with oil or fumes in the air.
(5) The place with sulfureted gas.
(6) Other places with special circumstances.
(7) The appliance shall not be installed in the laundry.
2. Grounding Requirement:
(1) The air conditioner is rst  class  electric  appliance.  It must 
be  properly  grounding with  specialized  grounding  device 
by a  professional. Please  make sure it  is always  grounded 
effectively, otherwise it may cause electric shock.
(2) The yellow-green  wire in air conditioner is grounding wire, 
which cant be used for other purposes.
(3) The  grounding  resistance  should  comply with  national 
electric safety regulations.
(4)  The  appliance  must  be  positioned  so  that  the  plug  is 
accessible.
(5) An all-pole disconnection switch having a contact separation 
of at least 3mm in all poles should be connected in xed wiring.
(6) Including an air switch with suitable capacity, please  note    
the  following table. Air  switch should  be  included magnet 
buckle and heating buckle function,  it  can protect the circuit-
short and overload. (Caution: please do not use the fuse only 
for protect the circuit)
1. Choosing Installation Iocation
Recommend  the  installation location  to the  client and  then 
conrm it with the client.
2. Install Wall-mounting Frame
(1)  Hang the  wall-mounting frame  on  the wall;  adjust  it  in 
horizontal position with the level meter and then  point out the 
screw xing holes on the wall.
(2) Drill the screw xing holes on the wall with impact drill (the 
specification of drill  head should be the  same  as the plastic 
expansion particle) and then ll the plastic expansion particles 
in the holes.
2. Indoor Unit:
(1) There should be no obstruction near air inlet and air outlet.
(2) Select a location where the condensation water can be 
dispersed easily and wont affect other people.
(3) Select a location which is convenient to connect the 
outdoor unit and near the power socket.
(4) Select a location which is out of reach for children.
(5) The location should be able to withstand the weight of 
indoor unit and wont increase noise and vibration.
(6) The appliance must be installed 2.5m above oor.
(7) Dont install the indoor unit right above the electric 
appliance.
(8) Please try your best to keep way from uorescent lamp.
3. Outdoor Unit:
(1) Select a location where the noise and outow air emitted by 
the outdoor unit will not affect neighborhood.
(2) The location should be well ventilated and dry, in which 
the outdoor unit wont be exposed directly to sunlight or strong 
wind.
(3) The location should be able to withstand the weight of 
outdoor unit.
(4) Make sure that the installation follows the requirement of 
installation dimension diagram.
(5) Select a location which is out of reach for children and far 
away from animals or plants.If it is unavoidable, please add 
fence for safety purpose.
Note:
Air-conditioner Air switch capacity
07/09K 10A
12/18K 16A
24K 25A