30
Technical Information
Service Manual
2.3 Cooling and Heating Data Sheet in Rated Frequency
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.
Cooling:
Heating:
Rated cooling condition(°C) (DB/WB)
Model
Pressure of gas pipe connecting
indoor and outdoor unit
Inlet and outlet pipe temperature of
heat exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
27/19 35/24 09K 0.8~1.1 12 ~ 15 65 ~ 38 Super High High
27/19 35/24 12K 0.9~1.1 12 ~ 14 75 ~ 37 Super High High
27/19 35/24 18K 0.9~1.1 12 ~ 14 75 ~ 37 Super High High
27/19 35/24 24K 0.9~1.1 12 ~ 14 75 ~ 37 Super High High
Rated heating condition(°C) (DB/WB)
Model
Pressure of gas pipe connecting
indoor and outdoor unit
Inlet and outlet pipe temperature of
heat exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6 09K 2.8~3.2 68 ~ 30 2 ~ 5 Super High High
20/- 7/6 12K 2.2~2.4 70 ~ 35 2 ~ 4 Super High High
20/- 7/6 18K 2.2~2.4 70 ~ 40 1 ~ 5 Super High High
20/- 7/6 24K 2.2~2.4 70 ~ 35 2 ~ 4 Super High High