2
Technical Information
Service Manual
Model GWHD(18)NK3FO
Product Code CB228W03500/CB228W03501
Power
supply
Rated Voltage V~ 220-240V
Rated Frequency Hz 50
Phases 1
Cooling capacity(max~min) W 5000(2050~6200)
Heating capacity(max~min) W 5600(2500~6650)
Cooling Power Input(max~min) W 1550(500~2550)
Heating Power Input(max~min) W 1550(580~2700)
Cooling Current Input A 6.88
Heating Current Input A 6.88
Rated Power Input W 2700
Rated Current A 11.98
SEER W/W 5.6
SCOP W/W 3.8
Outdoor
Unit
Compressor Trademark ZHUHAI LANDA COMPRESSOR CO.,LTD
Compressor Model QXA-B141zF030A
Compressor Refrigerant Oil Type RB68EP
Compressor Type Rotary
L.R.A A /
Compressor Rated Load Amp (RLA) A 7.2
Compressor Power Input W 1440
Compressor Thermal Protector 1NT11L-6233
Throttling Method Electron expansion valve
Cooling Operation Ambient Temperature Range
O
C -15~48
Heating Operation Ambient Temperature Range
O
C -15~24
Condenser Material Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7
Rows-Fin Gap(mm) mm 2-1.4
Coil length (l) X height (H) X coil width (L) mm 851X38.1X660
Fan Motor Speed (rpm) (H/M/L) rpm 630
Output of Fan Motor W 60
Fan Motor RLA A /
Fan Motor Capacitor μF /
Air Flow Volume of Outdoor Unit m
3
/h 3200
Fan Type-Piece Axial-ow
Fan Diameter mm Φ520
Defrosting Method Automatic Defrosting
Climate Type T1
Isolation I
Moisture Protection IP24
Permissible Excessive Operating Pressure for the
Discharge Side
MPa 4.3
Permissible Excessive Operating Pressure for the
Suction Side
MPa 2.5
Dimension (W/H/D) mm 963X700X396
Dimension of Package (L/W/H) mm 1026X455X735
Dimension of Package(L/W/H) mm 1029X458X750
Net Weight kg 50
Gross Weight kg 55
efrigerant Charge R410A
Refrigerant Charge kg 1.40