D Series Modular Air-cooled Scroll Chillers 
39
7.12 Precautions
(1) Take periodic maintenance to the unit to guarantee normal operation. 
(2) Once refrigerant leaks, shut down the unit immediately and contact the serviceman. No  open  re  is 
allowed in that refrigerant will decompose into toxic gas. 
(3) Switch o the main power supply in case of a re hazard and extinguish it with eective measures.
(4) The working environment shall be  far  away from the inammable substance, such as petroleum  and 
alcoholic etc. to avoid explosion.
(5) The unit is allowed restarted only after  any  malfunction is eliminated, otherwise refrigerant or chilled 
water would leak, in which case, it is imperative to turn o all switches or the main power supply. 
(6) Do not short-circuit the protection device, otherwise it would cause some malfunction. 
8 Troubleshooting
8.1 Error Lists and Troubleshooting Measures
Error Possible Causes Troubleshooting Measures
Too high 
discharge 
pressure
• 
There is air or other incondensable gas 
inside the system
• 
Fins of the condenser are dirty or 
clogged
• 
The air ow for condensing is insucient 
or the fan of the condenser runs 
improperly
• 
The suction pressure is too high
• 
Refrigerant is charged too much
• 
Ambient temperature is too high
• 
Expel incondensable air and vacuum the 
system if necessary
• 
Clean ns
• 
Repair the fan of the condenser
• 
See “Too high suction pressure”
• 
Let part of refrigerant out
Too low 
discharge 
pressure
• 
The suction pressure is too low
• 
Refrigerant leaks or is charged 
insuciently
• 
See “Too low suction pressure”
• 
Take leakage test and add refrigerant
Too high 
suction 
pressure
• 
The discharge pressure is too high
• 
Refrigerant is charged exceedingly
• 
Liquid refrigerant ows from the 
evaporator to the compressosr
• 
The entering chilled water temperature is 
higher than the allowable value
• 
See “Too high discharge pressure”
• 
Let the exceedance of refrigerant out
• 
Check and regulate the expansion valve 
and be sure the temperature sensor of the 
expansion valve is attached with the suction 
line closely and tightly insulated
Too low 
suction 
pressure
• 
The ambient temperature is too low
• 
The check valve or the drier-lter is 
clogged
• 
The expansion valve works improperly
• 
Refrigerant is insucient
• 
The entering chilled water is lower than 
the setpoint
• 
The chilled water ow is insucient
• 
Replace the check valve or the drier-lter
• 
Regulate the expansion valve properly or 
take a leakage test to the expansion valve
• 
Take a leakage test and add refrigerant
• 
Check the intallaiton
• 
Check the entering/leaving water pressure 
and regulate the water owrate
High 
pressure 
protection
• 
The ambient temperature is too high
• 
The air ow for condensing is insucient 
or the fan of the condenser malfunctions
• 
The high-pressure swtichs malfunctions
• 
Refrigerant is charged exceedingly
• 
Repair the fan of the condenser
• 
Check the high pressure switch
• 
Check the refrigeration charge and let the 
exceedance out