D Series Modular Air-cooled Scroll Chillers
39
7.12 Precautions
(1) Take periodic maintenance to the unit to guarantee normal operation.
(2) Once refrigerant leaks, shut down the unit immediately and contact the serviceman. No open re is
allowed in that refrigerant will decompose into toxic gas.
(3) Switch o󰀨 the main power supply in case of a re hazard and extinguish it with e󰀨ective measures.
(4) The working environment shall be far away from the inammable substance, such as petroleum and
alcoholic etc. to avoid explosion.
(5) The unit is allowed restarted only after any malfunction is eliminated, otherwise refrigerant or chilled
water would leak, in which case, it is imperative to turn o󰀨 all switches or the main power supply.
(6) Do not short-circuit the protection device, otherwise it would cause some malfunction.
8 Troubleshooting
8.1 Error Lists and Troubleshooting Measures
Error Possible Causes Troubleshooting Measures
Too high
discharge
pressure
There is air or other incondensable gas
inside the system
Fins of the condenser are dirty or
clogged
The air ow for condensing is insu󰀩cient
or the fan of the condenser runs
improperly
The suction pressure is too high
Refrigerant is charged too much
Ambient temperature is too high
Expel incondensable air and vacuum the
system if necessary
Clean ns
Repair the fan of the condenser
See “Too high suction pressure”
Let part of refrigerant out
Too low
discharge
pressure
The suction pressure is too low
Refrigerant leaks or is charged
insu󰀩ciently
See “Too low suction pressure”
Take leakage test and add refrigerant
Too high
suction
pressure
The discharge pressure is too high
Refrigerant is charged exceedingly
Liquid refrigerant ows from the
evaporator to the compressosr
The entering chilled water temperature is
higher than the allowable value
See “Too high discharge pressure”
Let the exceedance of refrigerant out
Check and regulate the expansion valve
and be sure the temperature sensor of the
expansion valve is attached with the suction
line closely and tightly insulated
Too low
suction
pressure
The ambient temperature is too low
The check valve or the drier-lter is
clogged
The expansion valve works improperly
Refrigerant is insu󰀩cient
The entering chilled water is lower than
the setpoint
The chilled water ow is insu󰀩cient
Replace the check valve or the drier-lter
Regulate the expansion valve properly or
take a leakage test to the expansion valve
Take a leakage test and add refrigerant
Check the intallaiton
Check the entering/leaving water pressure
and regulate the water owrate
High
pressure
protection
The ambient temperature is too high
The air ow for condensing is insu󰀩cient
or the fan of the condenser malfunctions
The high-pressure swtichs malfunctions
Refrigerant is charged exceedingly
Repair the fan of the condenser
Check the high pressure switch
Check the refrigeration charge and let the
exceedance out